SPECIFICATIONS FOR MEASUREMENT OF TANd/C
- Test frequency: 10 to 100Hz
- Maximum current: depends on external components (circuit breakers), standard is 10A, 50 mA and 2A also available.
- Reference capacitor: 1nF rated up to 20 kV at 23°C, correction in settings, see QA certificate for exact values.
- Tand: 10-5 (resolution)
- Error: Tand: 1-2⋅10-4 (uncertainty), Capacitance 0.5% at 5V input at 23°C.
- Display units: selected by user interface
- Power supply: USB (required for external power supply of PD module)
- Harmonics: numerically rejected by the software algorithm
- USB interface: PC requirement: desktop or laptop computer, Windows XP, 512 MB (min.)
- Voltage test range: 15kV (DELTAMAXX 15), 20kV (DELTAMAXX 20), 30kV (DELTAMAXX 30), 50kV (DELTAMAXX 50)
SPECIFICATIONS FOR PARTIAL DISCHARGE MEASUREMENT WITH INTEGRATED COUPLING CAPACITOR
- Test frequency: 10 to 100Hz (HV frequency range)
- Coupling capacitor: 1nF rated up to 20 kV at 23°C, see quality assurance documents.
- Coupler impedance: Built-in high voltage isolation transformer
- PD bandpass: designed according to IEC60270,40-800kHz
- PD ranges: depends on version and test object and noise, typical 10pC to 200nC
- Max. pulse rep. rate: 40kHz
- Display: phase-resolved partial discharge pattern
- Power supply: USB and external 6VDC power source
- USB interface: PC requirement: desktop or laptop computer, Windows XP, 512 MB (min.)
- Voltage test range: 15kV (DELTAMAXX 15), 20kV (DELTAMAXX 20), 30kV (DELTAMAXX 30), 50kV (DELTAMAXX 50)
Other products you may be interested in
-
DCR-60™
DCR 60- identifies stator ground wall insulation problems by off-line DC high voltage ramp test…
-
ELCID™ Evolution
ELCID Evolution allows off-line testing of interlaminar insulation breakdown within a stator core.
-
Stator Wedge Analyzer™
The SWA instrument allows maintenance personnel to easily and efficiently evaluate stator wedge clearances.
-
RIV 800 & Camera System
The Iris Power RIV800 Robotic Inspection Vehicle and Camera System allows a visual inspection of…